• Address - Must be located on the front & back of the building with a minimum size 5 inch numbers in contrasting colors to the background and must be visible from the street.
• Certificate of Occupancy Permit -All occupants are required to have a C of 0 and it must be posted in a visible location.
• Ceilings - In a sprinklered occupancy, all ceilings tiles must be in place.
• Cylinders & Bottles - All pressurized cylinders must be properly secured, either in a cylinder cart or chained to the wall.
• Door Locks - Doubled keyed locks, deadbolts, hasps, padlocks, bars, and chains shall not be installed on marked exits.
• Electrical Outlet & Switch Covers -Must be in place on all electrical devices.
• Electrical Panels - Shall have all open slots properly covered and 36 inches of clearance in front of all electrical panels.
• Electrical Power Strips -Can be used as an extension cord if they are circuit breaker protected. They must be plugged directly into a wall outlet (No daisy chaining).
• Electrical Rooms - Must be identified on the exterior of the door and cannot be used as storage areas.
• Emergency Lighting- Shall illuminate the means of egress and operate on battery (DC) power.
• Exit Corridor & Path - Shall maintain a minimum of 44 inches of clear path at all times for occupancies with over 50 people and 36 inches for occupancies with less than 50 people.
• Exit Signs - Shall be posted to show exit path. All exit bulbs shall operate on normal (AC) power and battery (DC) power.
• Extension Cords - Shall not be used for permanent wiring (Less than 90 days) and cannot run through walls, ceilings, doorways, floors, or windows.
• Fire Extinguishers - One for every 3,000 square feet and 75 feet of travel on every floor level. Minimum size 2A-IOBC secured visibly 3-5 feet off the floor. All fire extinguishers shall have a current inspection tag showing an inspection within the last year.
• Heating Equipment - Heating equipment must have proper clearance; 30 inches to access and 18 inches around perimeter.
• Idle Pallet Storage - Indoors, groups of 4 stacks, 6 feet tall, 8 feet apart from other groups, and 25 feet from combustibles.
• Means of Egress - Shall be an unobstructed and a continuous way of travel including the access to the exit, the exit itself, and the exit discharge.
• Sprinkler Clearance - Storage must remain at least 18 inches from sprinkler heads and 36 inches from early suppression fast response (ESFR) sprinkler heads.
• Sprinkler Heads - Shall be replaced when damaged, dirty, or painted. Must have a minimum of 3 replacement heads for each type used in occupant and one sprinkler wrench. All escutcheon collars must be in place.
• Sprinkler Rooms - Must be identified on the exterior of the door and cannot be used as a storage area.
• Sprinkler System Inspection -Shall have a current inspection tag showing an inspection within the last year.